Specifications
MODEL | ZEB-OU10KE16 | |
Phase | 1-phase in / 1-phase out | |
Capacity | 10000 VA 8000W | |
INPUT | ||
Nominal Voltage | 208/220/230/240VAC | |
Voltage Range | 110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%) | |
Frequency Range | 46~54 Hz or 56~64 Hz | |
Power Factor | ≥0.99 @ 100% Load | |
OUTPUT | ||
Output Voltage | 208/220/230/240VAC | |
AC Voltage Regulation (Batt. Mode) | ± 1% | |
Frequency Range (Synchronized Range) | 46~54Hz | |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz | |
Current Crest Ratio | 3:1 (max.) | |
Harmonic Distortion | ≦ 3 % THD (Linear Load) | |
≦ 5 % THD (Non-linear Load | ||
Transfer Time | AC Mode to Batt. Mode : Zero | |
Inverter to Bypass : Zero | ||
Waveform (Batt. Mode) | Pure Sine wave | |
EFFICIENCY | ||
AC Mode | 93.00% | |
BATT Mode | 91.00% | |
BATTERY | ||
Numbers | 16 ~ 20 (Adjustable)* | |
Typical Recharge Time | 9hrs recover to 90% capacity | |
Battery Type | SMF/VRLA | |
Charging Current (max.) | 1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries | |
Charging Voltage | 13.65 x N (N-Number of battery | |
INDICATORS | ||
LCD Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |
ALARM | ||
Battery Mode | Sounding every 4 seconds | |
Low Battery | Sounding every second | |
Overload | Sounding twice every second | |
Fault | Continuously sounding | |
PHYSICAL | ||
Dimension,DxWxH (mm) | 442 x 190 x 318 | |
Net Weight (kgs) | 16 |